We use cookies to improve your online experience. By continuing browsing this website, we assume you agree our use of cookies.
Your position: Home / Electronic Components / Capacitor

KRIWAN INT276 LC+ pressure vessel / oil separator special level monitoring switch with pressure head

INTLC+276
KRIWAN INT276 LC+ pressure vessel / oil separator special level monitoring switch with pressure head
Quantity:
-
+
(999986 available)
Shipping Cost:
to
Estimated Delivery Time:
Please select the country you want to ship from
Please select the information you wantX
  • Description
  • Reviews(144)
Specifications
brand KRIWAN
Model INT276LC+

This link is attached to the front pressure head! Without mechanical: 880 yuan /PCS

INT276LC liquid level monitor switch INT276LC level monitoring switch

application
Optical monitoring device INT276 LC for contactless liquid level monitoring. The realization of optical liquid level monitoring is accomplished by fixing the screw -s and the removable analysis specific components installed in the desired position. In the replacement analysis without the need to open the tank special -. The relay is connected to the power supply for about 3 seconds. When the liquid level is insufficient or the fault occurs, the relay is switched off after a period of time. When the fault or liquid level is raised to a sufficient area, the relay is delayed for a period of time. The normally open contact of zero potential can be directly closed in the safety control circuit without additional auxiliary relay.
INT276LC integrated optical self monitoring device improves work safety. Prevention of assembly errors or operational errors by carrying out installation inspection. The built-in LED displays the running ready state and displays a flashing code when there are other running states:
OK
* * * fault
The liquid level is too low
Installation instructions
assembling
Installation personnel must be based on the specific application to ensure the sealing of the transition point. The tightening torque of the screw in is about 75Nm. Inspection of electrical - (especially glass mirrors) to check whether they are clean. Insert the analysis - into the screw in and tighten it manually with the locking nut (tightening torque is about 10Nm). At the same time, attention must be paid to the position of the cable. Electrical connection according to the attached wiring diagram. The tank is filled again, check the screw sealing parts.
Screw in technical data
Allowable ambient temperature: -30 C ~ 60 C
Maximum temperature on cone: 80 DEG C
Pressure: 32 bar
Housing: VA 1.4510 or 1.4305
Connecting thread: M20x1.5 mm. - opening 24NPT1/2 - opening 24
Weight: about 75 grams
Analyze technical data of special components
Connect power supply (52S...) AC50/60Hz 230V 10%
Connect power supply (41S...) AC50/60Hz 115V 10%
Allowed environment: -30 C ~ 60 C
delay
Relay start: after the power supply voltage is turned on, the liquid level monitor is turned on for 3 seconds
Relay off (liquid level): 5 seconds after + 2 seconds
Relay off (fault): 5 seconds after + 2 seconds
Relay open (full level): after 5 seconds + + 2 seconds
Relay open (no fault). After 5 seconds + 2 seconds
Relay AC:250W, 2.5A C300
Mechanical life: about 105 slow cycle
Shell: ULtramid A3XZG5
Protection mode follows EN60529 standard: IP54 built-in state
Tighten nut
Connection electrical: 4xAWG18 (0.75 mm) L=1 m, color coded about 2
Weight: about 80 grams
Order description
230 volt version: INT276 LC liquid level monitoring device
Analysis of special components: 52S476S60
115 volt version: INT276LC liquid level monitoring device
Analysis of special components: 41S476S60
Screw in part: M20x1.5 mm 02K465
Screw in part: NPT1/2 02K460S22